Legacy Chillers - Products Legacy Chillers - Services On-line Store Affiliates Legacy Chillers - General Chiller Support Legacy Chillers - Quote Wizard Contact Legacy Chiller Systems
 
 
Knowledge Base Index
 * Legacy Economizer Systems 7 Articles 
 Chiller Buyer Resources 5 Articles 
 Chiller Capacity Tables 74 Articles 
 Chiller Industry Articles 37 Articles 
 Chiller Quote Wizard Training 10 Articles 
 Chiller System Installation 6 Articles 
 Chiller System Maintenance 2 Articles 
 Chiller Systems Design 14 Articles 
 Chiller Training Webinars 6 Articles 
 Chiller Troubleshooting 40 Articles 
 Legacy Affiliates Program 4 Articles 
 Legacy Customer Interests 9 Articles 
 Legacy Press Releases 4 Articles 
 Legacy Product Submittals 4 Articles 
 OEM - Service Bulletins 1 Articles 
 Tranter Heat Exchangers 1 Articles 
Top Ten Articles
Chiller loop piping system design
Chiller Installation, Startup, and Maintenance
Typical Refrigeration piping diagram
Understanding Chiller Refrigeration Principles
Glycol - Adding to chiller loop
Sporlan - Using a T-P chart as a troubleshooting tool
Chiller Systems Recommended Maintenance
Chiller System Design and use of SystemSyzer software by Legacy Chiller Systems
Closed Loop Chiller System - Automatic Air Vents
Understanding Chiller Refrigeration Cycle
My Recently Viewed Articles
Chiller Systems - Head Pressure Control Information
PWC-PWCT72D-WATERCOOLED-Capacity table
PAC-PACT70S-AIRCOOLED-Capacity table
PAC-PACT140D-AIRCOOLED-Capacity table
Centrifugal Pumps - Volute Pump
Knowledge Base Search
Keywords  
Article Type  
Chiller Systems - Head Pressure Control Information

SUMMARY
This article covers the basics of head pressure controls in chiller systems.

RESOLUTION
Attached article summary:

Condenser capacities are based, in part, on TD (temper-ature difference) between the ambient and the refriger-ant condensing temperature. As the ambient falls, and the TD increases, the condenser capacity will increase.For example, a condenser rated at 150,000 Btu/h at a110ºF and 10ºF TD, would have a capacity of 750,000Btu/h with a 50ºF TD. In laymen’s terms, it has nowbecome five times larger than it needs to be. An over-sized condenser means lower head pressure, andreduced electrical consumption.

When the actual ambient is below the design ambient, we can take advantage of the now greater condenser capacity, allow the head pressure to fall, and start reaping thebenefits—to a point. Too much of any good thing can become problematic, and reducing head pressure is no exception.

If the head pressure is allowed to fall below certain minimums,system performancecan be adversely affected in the following areas:

1.Underfeeding TEVs (thermostatic expansionvalves) and starving evaporators.

2.Oil logging.

3.Reduced compressor efficiency and higher dis-charge temperatures.

Please see attached PDF for complete article.

RELATED DOCUMENTS

  • Article - Understanding the fundamentals of head pressure control. Click to browse this file.

  • Posted 12/25/2005 :: 4838 views
     
    Related Articles
    Sporlan - Using a T-P chart as a troubleshooting tool
    Refrigeration Engineering Quick Reference Guide
    T-P chart pocket size
    Need Chiller Pricing?

    Get a price on your next chiller project
    Access over one hundred sixty chiller models, hundreds of options and get a quote in tens minutes or less. Find out more »

    Featured Affiliate
    Design HVAC,Inc.
    HVAC Design,LEED Building HVAC Design and Commissioning.Service,Installation and Maintenance.Super High Efficient Boilers and Chillers

    Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

    Home | Products | Services | On-line Store | Affiliates | Support | Contact | Site Map | Join Us on Facebook

    Questions or problems regarding this web site should be directed to support@Legacychillers.com.
    Copyright © <%= year(now)%> Legacy Chiller Systems (USA). All rights reserved.
    Toll free within USA/CANADA  - 877-988-5464