Legacy Chillers - Products Legacy Chillers - Services On-line Store Affiliates Legacy Chillers - General Chiller Support Legacy Chillers - Quote Wizard Contact Legacy Chiller Systems
 
 
Knowledge Base Index
 * Legacy Economizer Systems 7 Articles 
 Chiller Buyer Resources 5 Articles 
 Chiller Capacity Tables 74 Articles 
 Chiller Industry Articles 37 Articles 
 Chiller Quote Wizard Training 10 Articles 
 Chiller System Installation 6 Articles 
 Chiller System Maintenance 2 Articles 
 Chiller Systems Design 14 Articles 
 Chiller Training Webinars 6 Articles 
 Chiller Troubleshooting 40 Articles 
 Legacy Affiliates Program 4 Articles 
 Legacy Customer Interests 9 Articles 
 Legacy Press Releases 4 Articles 
 Legacy Product Submittals 4 Articles 
 OEM - Service Bulletins 1 Articles 
 Tranter Heat Exchangers 1 Articles 
Top Ten Articles
Chiller loop piping system design
Chiller Installation, Startup, and Maintenance
Typical Refrigeration piping diagram
Understanding Chiller Refrigeration Principles
Glycol - Adding to chiller loop
Sporlan - Using a T-P chart as a troubleshooting tool
Chiller Systems Recommended Maintenance
Chiller System Design and use of SystemSyzer software by Legacy Chiller Systems
Closed Loop Chiller System - Automatic Air Vents
Understanding Chiller Refrigeration Cycle
My Recently Viewed Articles
Micro processor - Dual Compressor Lag Lead
Copper Piping Water Velocity Limits
Chiller Problem - Microprocessor Pressure Transducer Error
RSES Journal June 2007 - EPA and Greenhouse Gases Regulations
PAC-SEMI-351S2S-AIRCOOLED-Capacity table
Variable condenser fan speed control
PWC360D-WATERCOOLED-Capacity table
Toshiba Medical America Systems (TAMS) - No longer selling chillers for MRI
Chiller Problems - Water Heating Up
Goulds Pump Curves And Other Information
Knowledge Base Search
Keywords  
Article Type  
Micro processor - Dual Compressor Lag Lead

SUMMARY
Micro processor - Dual Compressor Lag Lead. Understanding how it works.

SYMPTOMS
On a dual compressor system CP2 may start on a first stage cooling call.

CAUSE
The chillers micro-process controller logs total run hours of each compressor. From a NO call condition, when process fluid gets to SP1 + dif1 the micro-processor will perform a call for cooling. At this time it will review the compressor that has less running hours. For that cycle, the compressor with less running hours will be the LEAD compressor.

Technician should be aware of the automatic lag lead function of our micro-processors when performing diagnostics. During service, to assure that both compressors run, we recommend setting both SP1, SP2 at the same temp.

Note: Compressor hours can be seen in the micro-processor review mode as the "HR" parameter. Keep in mind that compressor run hours will be the displayed digits x 10. For example: An HR reading of 10 indicates 100 hours of compressor run time.

Posted 11/4/2009 :: 863 views
 
Related Articles
Chiller Installation, Startup, and Maintenance
Need Chiller Pricing?

Get a price on your next chiller project
Access over one hundred sixty chiller models, hundreds of options and get a quote in tens minutes or less. Find out more »

Featured Affiliate
Design HVAC,Inc.
HVAC Design,LEED Building HVAC Design and Commissioning.Service,Installation and Maintenance.Super High Efficient Boilers and Chillers

Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

Home | Products | Services | On-line Store | Affiliates | Support | Contact | Site Map | Join Us on Facebook

Questions or problems regarding this web site should be directed to support@Legacychillers.com.
Copyright © <%= year(now)%> Legacy Chiller Systems (USA). All rights reserved.
Toll free within USA/CANADA  - 877-988-5464