Legacy Chillers - Products Legacy Chillers - Services On-line Store Affiliates Legacy Chillers - General Chiller Support Legacy Chillers - Quote Wizard Contact Legacy Chiller Systems
 
 
Knowledge Base Index
 * Legacy Economizer Systems 7 Articles 
 Chiller Buyer Resources 5 Articles 
 Chiller Capacity Tables 74 Articles 
 Chiller Industry Articles 37 Articles 
 Chiller Quote Wizard Training 10 Articles 
 Chiller System Installation 6 Articles 
 Chiller System Maintenance 2 Articles 
 Chiller Systems Design 14 Articles 
 Chiller Training Webinars 6 Articles 
 Chiller Troubleshooting 40 Articles 
 Legacy Affiliates Program 4 Articles 
 Legacy Customer Interests 9 Articles 
 Legacy Press Releases 4 Articles 
 Legacy Product Submittals 4 Articles 
 OEM - Service Bulletins 1 Articles 
 Tranter Heat Exchangers 1 Articles 
Top Ten Articles
Chiller loop piping system design
Chiller Installation, Startup, and Maintenance
Typical Refrigeration piping diagram
Understanding Chiller Refrigeration Principles
Glycol - Adding to chiller loop
Sporlan - Using a T-P chart as a troubleshooting tool
Chiller Systems Recommended Maintenance
Chiller System Design and use of SystemSyzer software by Legacy Chiller Systems
Closed Loop Chiller System - Automatic Air Vents
Understanding Chiller Refrigeration Cycle
My Recently Viewed Articles
Short on Temperature Sensor
NEMA - IEC Enclosure Standards
Remote chiller and system pump Start Stop
Chillers and Data Centers -Data Centers - Heat Containment offered by Legacy Chiller Systems
Chiller Quote Wizard Video - Select Package Chiller or Split Chiller
ICM Variable Condenser Fan Controller Information
Micro processor - dual stage replacement
Centrifugal Pumps - design, dimensions, & standards
RSES Journal - Diagnostics using a pressure-temperature chart (P-T)
Temperature Sensors - How to Test
Knowledge Base Search
Keywords  
Article Type  
Short on Temperature Sensor

SYMPTOMS
What happens is if there is a short internally on the temperature sensor from the +3.5v to ground, this will cause the Controller's power supply to be pulled down, which inturn will reboot the controller. If left in this condition, it would more then likely cause the Controller to stop working all together after a little while. This is a hardware failure.

If the temperature sensor was not shorted and functioning correctly, just sending a temperature reading that is out of range, this would cause a temperature error on the Controller.

RESOLUTION
To check the temperature sensor with an ohm meter do the following:

Set your meter to read ohms.

With the temperature sensor disconnected from the Controller measure pin 1 (red) to pin 3 (black) on the sensor plug itself. The value the meter reads should be a very high value = > 10,000 ohms.

With the temperature sensor disconnected from the Controller measure pin 2 (white) to pin 3 (black) on the sensor plug itself.
The value the meter reads should be a very high value = > 10,000 ohms.

In the same manner check pin 1 (red) to the brass sensor cover, then pin 2 (white) to the brass sensor cover, then pin 3 (black) to the brass sensor cover.

None of these measurements should be below 10,000 ohms.

Posted 2/16/2009 :: 730 views
Need Chiller Pricing?

Get a price on your next chiller project
Access over one hundred sixty chiller models, hundreds of options and get a quote in tens minutes or less. Find out more »

Featured Affiliate
Design HVAC,Inc.
HVAC Design,LEED Building HVAC Design and Commissioning.Service,Installation and Maintenance.Super High Efficient Boilers and Chillers

Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

Home | Products | Services | On-line Store | Affiliates | Support | Contact | Site Map | Join Us on Facebook

Questions or problems regarding this web site should be directed to support@Legacychillers.com.
Copyright © <%= year(now)%> Legacy Chiller Systems (USA). All rights reserved.
Toll free within USA/CANADA  - 877-988-5464