Legacy Chillers - Products Legacy Chillers - Services On-line Store Affiliates Legacy Chillers - General Chiller Support Legacy Chillers - Quote Wizard Contact Legacy Chiller Systems
 
 
Knowledge Base Index
 * Legacy Economizer Systems 7 Articles 
 Chiller Buyer Resources 5 Articles 
 Chiller Capacity Tables 74 Articles 
 Chiller Industry Articles 37 Articles 
 Chiller Quote Wizard Training 10 Articles 
 Chiller System Installation 6 Articles 
 Chiller System Maintenance 2 Articles 
 Chiller Systems Design 14 Articles 
 Chiller Training Webinars 6 Articles 
 Chiller Troubleshooting 40 Articles 
 Legacy Affiliates Program 4 Articles 
 Legacy Customer Interests 9 Articles 
 Legacy Press Releases 4 Articles 
 Legacy Product Submittals 4 Articles 
 OEM - Service Bulletins 1 Articles 
 Tranter Heat Exchangers 1 Articles 
Top Ten Articles
Chiller loop piping system design
Chiller Installation, Startup, and Maintenance
Typical Refrigeration piping diagram
Understanding Chiller Refrigeration Principles
Glycol - Adding to chiller loop
Sporlan - Using a T-P chart as a troubleshooting tool
Chiller Systems Recommended Maintenance
Chiller System Design and use of SystemSyzer software by Legacy Chiller Systems
Closed Loop Chiller System - Automatic Air Vents
Understanding Chiller Refrigeration Cycle
My Recently Viewed Articles
Phase reversal
Open Loop Chiller Systems Training by Legacy Chiller Systems
PAC-SEMI-301S2S-AIRCOOLED-Capacity table
Global Warming - Newsweek 2007
Hydrogen From Algae - Article posted by Legacy Chiller Systems
Chiller Economizer Introduction and Operation by Legacy Chillers
RSES Journal - March 2006 - Refrigerant Blends - P-T Charts and Troubleshooting
Video - Chiller Energy Usage Audit Tool - Survey Template
PWC-PWCT96D-WATERCOOLED-Capacity table
Receiver valves closed
Knowledge Base Search
Keywords  
Article Type  
Phase reversal

SYMPTOMS
Scroll compressor running but is loud with poor cooling and pumping performance.

CAUSE
This condition commonly occurs at startup. When the chiller is run tested at the factory, there is a 50% change that your building power will be orientated the same as the factory. If your building is out of phase with the chillers factory orientation, all three phase components, such as pumps and scroll compressors WILL run backwards.

After initial startup, it is possible for a chiller to begin running backwards if ANY two legs of main supply power are reversed at any time. Common items that can cause this are: Replacement of a breaker, replacement of a main or sub electrical distribution panel.


Other than abnormally loud Scroll operation, there is no way to physically confirm that a scroll is turning in the wrong direction. Using commonly available test equipment however, this can be easily confirmed by:

1. Checking the chiller suction and head pressures. If your scroll is running in reverse, you can expect higher than normal suction pressure and lower than normal head pressure.
2. Using an amp clamp, the compressors amp draw will be abnormally low.

Note: The specific reading you can expect have not been provided since the values will vary greatly depending on operating conditions. The factory recommends using readings taken as part of startup or maintenance for an operational baseline.


Another indicator of a phase reversal would be your pump. Using a nylon wire tie you can CAREFULLY insert the pointed end of the tie into the pump motors air fan towards the back of the pump motor. If the tie end goes up, the pump is turning clockwise (CW) and of the tie end goes down the pump is turning counter clockwise (CCW). On the stainless steel pump housing, there is an embossed arrow indicating proper rotation. Using the confirmed pump rotation, you can determine if the pump is rotating the proper direction – or not. Since all three-phase components are designed to run the same direction, there is a very good chance if one component is running the wrong direction they all are.

RESOLUTION
How to correct phase reversal: Reverse any two legs of main supply power entering the chiller. This can be done at the breaker, service disconnect or at the chillers high voltage single point wiring connection.

NOTE: RUNNING A SCROLL COMPRESSOR IN REVERSE WILL CAUSE DAMAGE TO THE SCROLL

APPLIES TO
ALL THREE-phase models

Posted 7/12/2007 :: 1819 views
Need Chiller Pricing?

Get a price on your next chiller project
Access over one hundred sixty chiller models, hundreds of options and get a quote in tens minutes or less. Find out more »

Featured Affiliate
Design HVAC,Inc.
HVAC Design,LEED Building HVAC Design and Commissioning.Service,Installation and Maintenance.Super High Efficient Boilers and Chillers

Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

Home | Products | Services | On-line Store | Affiliates | Support | Contact | Site Map | Join Us on Facebook

Questions or problems regarding this web site should be directed to support@Legacychillers.com.
Copyright © <%= year(now)%> Legacy Chiller Systems (USA). All rights reserved.
Toll free within USA/CANADA  - 877-988-5464