Water loop piping system design
Chiller Installation, Startup, and Maintenance
Glycol - Adding to chiller loop
Closed Loop Chiller System - Automatic Air Vents
Chiller Systems Recommended Maintenance
Chiller System Microprocessor Programming
Chiller Problems - Microprocessor Low Pressure error
Chiller Systems - Starting your Chiller
Chiller Systems - Flooded Condenser Valves
Chiller Problems - Microprocessor Low Flow error
My Recently Viewed Articles
Compressor Hot Gas Bypass (HGBP) heating water
Knowledge Base Search
Keywords  
Article Type  
Compressor Hot Gas Bypass (HGBP) heating water

SYMPTOMS
When microprocessor set point (SP1,SP2) is set below 45F, the chiller runs constant and appears to be heating water rather than cooling. Gylcol freeze protection may have been also added to the system.

CAUSE
All Legacy Chillers are tested and set up at the time they leave the factory to run water only. This is done to protect the chiller from freezing should a user drop the SP set point(s) below 45F prior to adding glycol freeze protection to the system.

When the SP set point(s) are programmed below 45F without adding glycol and setting the chiller up to run glycol the chillers HOT GAS BYPASS (HGBP) system will attempt to maintain approximately 54 PSI by bypassing HOT compressor discharge gas into the chillers evaporator. Under some operating conditions this (HGBP) can cause the chiller loop to heat and not cool.

RESOLUTION
If your process requires running your chiller loop colder than 45F, the proper concentration of glycol must be added to your system. When glycol is added to any chiller adjustments must be made to: The LP safety trip point(s), HGBP deployment pressure, low flow differential pressure switch and in some cases the TXV superheat settings.

MORE INFORMATION
See KB article “Glycol - Adding to chiller loop” for a step-by-step procedure on how to set your chiller up to run gycol.

APPLIES TO
All chiller models

Posted 7/12/2007 :: 483 views
 
Related Articles
Glycol - Adding to chiller loop

Need instant sales support?

Call our TOLL FREE support line: 1-877-988-5464

OR

Live chat by BoldchatPlus
CRM by Boldcenter

Need a FAST quote??

 

CLICK HERE

To register or login to your Quote Wizard account and save up to 40%


Order your CDKEY catalog TODAY!

Featured Affiliate
UsedChillerStore.com

For both Buyers and Sellers this site offers a NO COST, Effective and Easy alternative to expensive auction sites or resellers who charge commissions. Our goal is to provide sellers an way to expose their used chiller equipment to a vast numbers of qualified buyers while giving buyers the ability to locate the equipment they need as quickly as possible.


Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

Home | Chiller Solutions | Fluid Solutions | On-line Store | Affiliates | General Support | Contact Us | Site Map | Links
Questions or problems regarding this web site should be directed to support@Legacychillers.com.
Copyright © 2007 Legacy Chiller Systems (USA). All rights reserved.
Toll free within USA/CANADA  - 877-988-5464