Water loop piping system design
Chiller Installation, Startup, and Maintenance
Glycol - Adding to chiller loop
Closed Loop Chiller System - Automatic Air Vents
Chiller Systems Recommended Maintenance
Chiller Problems - Microprocessor Low Pressure error
Chiller System Microprocessor Programming
Chiller Systems - Starting your Chiller
Chiller Problems - Microprocessor Low Flow error
Chiller Systems - Flooded Condenser Valves
My Recently Viewed Articles
Pump over amping
Knowledge Base Search
Keywords  
Article Type  
Pump over amping

SYMPTOMS
System or tank re-circulation pumps starts and run. After operating for a varied amount of time, pumps turn off.

CAUSE
Between the main power buss, where power comes into the chiller, and the pump motor there will typically be several places in the electrical circuit where power can be interrupted. These are: Wires, fuses, motor starters and internal motor winding protectors. Any of these can cause a pump shutdown.

RESOLUTION
Before starting any troubleshooting ALWAYS TURN THE POWER OFF FIRST!. With power off at the chiller main service disconnect, perform the following checks:

1.Check (tighten as needed) all wire connections between the main power buss and pump.

2.Make a note of the pumps SF amps indicated on the pump motors nomenclature sticker. If your chiller is equipped with a motor starter, make sure the amp setting on the motor starters overload adjustment is set to match the pumps SP amps. If it is not, lift the plastic dust cover and adjust using the proper sized screwdriver.

3. Restart the chiller and pump(s).

4. Using an amp clamp, check the running amp draw pump(s). If the running amp draw is greater than SF amps, reduce fluid flow through the pump until your running amp draw is at or below SP amps.

5. Make sure your pump(s) are turning the correct direction.

Posted 3/13/2006 :: 523 views
 
Related Articles
Chiller Installation, Startup, and Maintenance
Chiller Systems - Starting your Chiller

Need instant sales support?

Call our TOLL FREE support line: 1-877-988-5464

OR

Live chat by BoldchatPlus
CRM by Boldcenter

Need a FAST quote??

 

CLICK HERE

To register or login to your Quote Wizard account and save up to 40%


Order your CDKEY catalog TODAY!

Featured Affiliate
UsedChillerStore.com

For both Buyers and Sellers this site offers a NO COST, Effective and Easy alternative to expensive auction sites or resellers who charge commissions. Our goal is to provide sellers an way to expose their used chiller equipment to a vast numbers of qualified buyers while giving buyers the ability to locate the equipment they need as quickly as possible.


Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

Home | Chiller Solutions | Fluid Solutions | On-line Store | Affiliates | General Support | Contact Us | Site Map | Links
Questions or problems regarding this web site should be directed to support@Legacychillers.com.
Copyright © 2007 Legacy Chiller Systems (USA). All rights reserved.
Toll free within USA/CANADA  - 877-988-5464