Chiller System Problem – Microprocessor 999 error code

SUMMARY This article teaches you what to do when your chiller’s microprocessor returns a 999 error code. This error is often cause by a voltage spike that has corrupted the internal programming. SYMPTOMS Chiller microprocessor controller shows a “999” error code. In some cases the chillers compressor(s) may remain running below the desired set point. […]

Chiller Problem – Microprocessor Pressure Transducer Error

SUMMARY This article describes how to fix a chiller with a microprocessor that is not receiving proper input signal from the pressure transducer. SYMPTOMS Microprocessor shows an �Err� on the top screen and a pressure transducer error code on the bottom screen. Pressure transducer errors include: “tL1” for compressor 1 low-pressure sensor error. “tL2” for […]

Chiller System Problems – Micro-processor won’t respond

SUMMARY This article teaches you what to do when your chiller system’s micro-processor won’t respond to programming mode. SYMPTOMS Pressing correct buttons to get into programming mode but the micro-processor won’t respond. CAUSE micro-processor is unable to confirm programming mode access request. RESOLUTION If holding the UP/DN buttons for 3-5 seconds does not change the […]

Variable condenser fan speed control

SYMPTOMS Chillers equipped with variable condenser fan speed control is tripping on high head pressure (Hi1) fault. Condenser fan(s) are not working properly. CAUSE ICM condenser variable fan speed control is not set properly or has been modified from factory settings. Control sensor(s) may not be secured to the proper location. RESOLUTION The attached PDF […]