Legacy Chillers - Products Legacy Chillers - Services On-line Store Affiliates Legacy Chillers - General Chiller Support Legacy Chillers - Quote Wizard Contact Legacy Chiller Systems
 
 
Knowledge Base Index
 * Legacy Economizer Systems 6 Articles 
 Chiller Buyer Resources 4 Articles 
 Chiller Capacity Tables 74 Articles 
 Chiller Industry Articles 37 Articles 
 Chiller Quote Wizard Training 10 Articles 
 Chiller System Installation 5 Articles 
 Chiller System Maintenance 2 Articles 
 Chiller Systems Design 14 Articles 
 Chiller Training Webinars 6 Articles 
 Chiller Troubleshooting 40 Articles 
 Legacy Affiliates Program 4 Articles 
 Legacy Customer Interests 9 Articles 
 Legacy Press Releases 2 Articles 
 Legacy Product Submittals 4 Articles 
 OEM - Service Bulletins 1 Articles 
Top Ten Articles
Chiller loop piping system design
Chiller Installation, Startup, and Maintenance
Glycol - Adding to chiller loop
Typical Refrigeration piping diagram
Chiller Systems Recommended Maintenance
Closed Loop Chiller System - Automatic Air Vents
Sporlan - Using a T-P chart as a troubleshooting tool
Chiller System Design and use of SystemSyzer software by Legacy Chiller Systems
Understanding Chiller Refrigeration Principles
Chiller Problems - Microprocessor Low Flow error
My Recently Viewed Articles
Chiller System Problems - Excessive Noise
Micro-Processor showing 32 and 32
PWC500D-WATERCOOLED-Capacity table
PAC-SEMI-150S2S-AIRCOOLED-Capacity table
PAC-PACT24S-AIRCOOLED-Capacity table
Understanding Chiller Refrigeration Principles
PAC-PACT100D-AIRCOOLED-Capacity table
Running a chiller on generator power
Knowledge Base Search
Keywords  
Article Type  
Chiller System Problems - Excessive Noise

SUMMARY
This article provides the information of how to fix a chiller system when it is producing excessive noise on startup. The most common cause of this problem is the compressor’s internal scroll running backwards.

SYMPTOMS
Compressor making excessive noise at startup.

CAUSE
Three phase scroll compressor running backwards.

RESOLUTION
Condition normally occurs at initial startup of chiller. Most common cause is the compressor’s internal scroll running backwards. Most likely, all other three phase motors within the chiller will be running the wrong direction as well.

To correct this problem, switch any two legs on the CHILLERS three phase power buss. This will cause all three phase motors to turn the correct direction and should eliminate the excessive compressor noise.

APPLIES TO
All three phase chiller models

Posted 1/4/2006 :: 1928 views
 
Related Articles
Chiller Installation, Startup, and Maintenance
Chiller Systems - Starting your Chiller
Featured Affiliate
Design HVAC,Inc.
HVAC Design,LEED Building HVAC Design and Commissioning.Service,Installation and Maintenance.Super High Efficient Boilers and Chillers

Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

Home | Products | Services | On-line Store | Affiliates | Support | Contact | Site Map
Questions or problems regarding this web site should be directed to support@Legacychillers.com.
Copyright © 2010 Legacy Chiller Systems (USA). All rights reserved.
Toll free within USA/CANADA  - 877-988-5464