Legacy Chillers - Products Legacy Chillers - Services On-line Store Affiliates Legacy Chillers - General Chiller Support Legacy Chillers - Quote Wizard Contact Legacy Chiller Systems
 
 
Knowledge Base Index
 * Legacy Economizer Systems 6 Articles 
 Chiller Buyer Resources 4 Articles 
 Chiller Capacity Tables 74 Articles 
 Chiller Industry Articles 37 Articles 
 Chiller Quote Wizard Training 10 Articles 
 Chiller System Installation 5 Articles 
 Chiller System Maintenance 2 Articles 
 Chiller Systems Design 14 Articles 
 Chiller Training Webinars 6 Articles 
 Chiller Troubleshooting 40 Articles 
 Legacy Affiliates Program 4 Articles 
 Legacy Customer Interests 9 Articles 
 Legacy Press Releases 2 Articles 
 Legacy Product Submittals 4 Articles 
 OEM - Service Bulletins 1 Articles 
Top Ten Articles
Chiller loop piping system design
Chiller Installation, Startup, and Maintenance
Glycol - Adding to chiller loop
Typical Refrigeration piping diagram
Chiller Systems Recommended Maintenance
Closed Loop Chiller System - Automatic Air Vents
Sporlan - Using a T-P chart as a troubleshooting tool
Chiller System Design and use of SystemSyzer software by Legacy Chiller Systems
Understanding Chiller Refrigeration Principles
Chiller Problems - Microprocessor Low Flow error
My Recently Viewed Articles
Running a chiller on generator power
PAC-SEMI-1200D-AIRCOOLED-Capacity table
National Geographic - Biofuels
Understanding Chiller Refrigeration Principles
Basic Chiller System layout and design by Legacy Chiller Systems
PAC-SEMI-150S2S-AIRCOOLED-Capacity table
PWC-PWCT90S-WATERCOOLED-Capacity table
Water Cooled Condenser Design Flow Rate Issues
Upgrade to new remote micro
PAC-PACT24S-AIRCOOLED-Capacity table
Knowledge Base Search
Keywords  
Article Type  
Running a chiller on generator power

SUMMARY
Although it is generally not recommended you run a chiller on generator power, this article may act as a list of requirements you will need if you intend on doing so.

SYMPTOMS
Running a chiller on generator power can be problematic and is not recommended as a general rule.

In a commercial/industrial environment, end users tend to hook up multiple loads to a single generator. As loads come on and off line, substantial power fluctuations in the generators output can occur. These fluctuations can cause abnormal stress on motor windings resulting in damage.

For sites that require emergency generator power, such as airports or medical facilities, great care must be taken in selecting the proper type and capacity generator.

End users who need their Legacy Chiller Systems to operate on generator power are advised to:

1. Make sure the generator can produce 125% of the total circuit FLA.

2. Make sure the generator has the capability of line conditioning that will assure clean power delivery to loads. Conditioning should include voltage, phase and harmonic protection. Overall, the generator should deliver power that meets or exceeds power standards of the local utility.

3. Install phase monitors on all critical mechanical equipment. Legacy Chiller Systems offers and excellent voltage and phase protection module (see below) that can be installed either at the factory prior to shipment or field retrofit. IMPORTANT: FAILURE OF A CHILLERS ELECTRICAL COMPOENTS BY WAY OF GENERATOR OPERATION IS NOT COVERED BY THE LIMITED WARRANTY.

4. Purchase insurance coverage for loss of equipment related generator power issues. If your facility requires deployment of generators, it would be advisable to contact your commercial insurer regarding a loss rider that covers for equipment damage caused by a generator.

Discussion: Most utility companies are required to meet minimum standards when power is delivered by way of normal utility owned transmission lines also known as “The Grid”. As part of the contract to sell power within a municipality, utility companies are required to warrant against equipment damage should the delivered power fall outside the agreed standards. Systems running on generator power would obviously bypass this coverage. For this reason, supplemental insurance to cover such damage is highly recommended.

RELATED DOCUMENTS

  • ICM VOLTAGE AND PHASE MONITOR Click to browse this file.

  • Posted 3/5/2007 :: 1486 views
    Featured Affiliate
    Design HVAC,Inc.
    HVAC Design,LEED Building HVAC Design and Commissioning.Service,Installation and Maintenance.Super High Efficient Boilers and Chillers

    Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

    Home | Products | Services | On-line Store | Affiliates | Support | Contact | Site Map
    Questions or problems regarding this web site should be directed to support@Legacychillers.com.
    Copyright © 2010 Legacy Chiller Systems (USA). All rights reserved.
    Toll free within USA/CANADA  - 877-988-5464