Legacy Chillers - Products Legacy Chillers - Services On-line Store Affiliates Legacy Chillers - General Chiller Support Legacy Chillers - Quote Wizard Contact Legacy Chiller Systems
 
 
Knowledge Base Index
 * Legacy Economizer Systems 7 Articles 
 Chiller Buyer Resources 5 Articles 
 Chiller Capacity Tables 74 Articles 
 Chiller Industry Articles 37 Articles 
 Chiller Quote Wizard Training 10 Articles 
 Chiller System Installation 6 Articles 
 Chiller System Maintenance 2 Articles 
 Chiller Systems Design 14 Articles 
 Chiller Training Webinars 6 Articles 
 Chiller Troubleshooting 40 Articles 
 Legacy Affiliates Program 4 Articles 
 Legacy Customer Interests 9 Articles 
 Legacy Press Releases 4 Articles 
 Legacy Product Submittals 4 Articles 
 OEM - Service Bulletins 1 Articles 
 Tranter Heat Exchangers 1 Articles 
Top Ten Articles
Chiller loop piping system design
Chiller Installation, Startup, and Maintenance
Typical Refrigeration piping diagram
Understanding Chiller Refrigeration Principles
Glycol - Adding to chiller loop
Sporlan - Using a T-P chart as a troubleshooting tool
Chiller Systems Recommended Maintenance
Chiller System Design and use of SystemSyzer software by Legacy Chiller Systems
Closed Loop Chiller System - Automatic Air Vents
Understanding Chiller Refrigeration Cycle
My Recently Viewed Articles
Chiller System Problems - HTA & LTA alarms
Closed Loop Chiller System Training by Legacy Chiller Systems
Electrical Definitions, Terms, and Formulas
Chiller Quote Wizard Video - Specialty Chillers for OEM
Chiller Systems Microprocessor Replacement
PAC-SEMI-440D2S-AIRCOOLED-Capacity table
PWC-PWCT240D-WATERCOOLED-Capacity table
PAC-SEMI-500D2S-AIRCOOLED-Capacity table
Affiliates program - Setup of a Featured Affiliate Add
Compressor Warranty
Knowledge Base Search
Keywords  
Article Type  
Chiller System Problems - HTA & LTA alarms

SUMMARY
This article describes what to do when there is an HTA alarm followed by an LTA alarm.

SYMPTOMS
HTA is indicated on micro display. After 5 seconds or so, the LTA comes on. I cannot change any set points through programming mode either. Also, I have just replaced both sensors thinking they were the initial trouble.

CAUSE
By the chiller return temperature exceeding the HTA set point. The LTA alarm was probably generated by fluid temp leaving the chiller as it got colder through the chillers refrigeration system. In both cases, the HTA Set point and LTA set point are to close to the chillers programmed set point.

RESOLUTION
Recommended set point for these alarms:

LTA = SP1 set point -10F
HTA = SP1 set point +15F


It is also important to note that when replacing sensors the location if important. Before doing any reprogramming of micro processor controller, be sure to verify the location of the temperature sensors and make sure they are insulated.

Note: To clear an HTA or LTA alarm momentarily press the chillers power button.

Posted 10/25/2006 :: 2347 views
 
Related Articles
Chiller Installation, Startup, and Maintenance
Need Chiller Pricing?

Get a price on your next chiller project
Access over one hundred sixty chiller models, hundreds of options and get a quote in tens minutes or less. Find out more »

Featured Affiliate
Design HVAC,Inc.
HVAC Design,LEED Building HVAC Design and Commissioning.Service,Installation and Maintenance.Super High Efficient Boilers and Chillers

Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

Home | Products | Services | On-line Store | Affiliates | Support | Contact | Site Map | Join Us on Facebook

Questions or problems regarding this web site should be directed to support@Legacychillers.com.
Copyright © <%= year(now)%> Legacy Chiller Systems (USA). All rights reserved.
Toll free within USA/CANADA  - 877-988-5464