Water loop piping system design
Chiller Installation, Startup, and Maintenance
Glycol - Adding to chiller loop
Closed Loop Chiller System - Automatic Air Vents
Chiller Systems Recommended Maintenance
Chiller Problems - Microprocessor Low Pressure error
Chiller System Microprocessor Programming
Chiller Systems - Starting your Chiller
Chiller Problems - Microprocessor Low Flow error
Chiller Systems - Flooded Condenser Valves
My Recently Viewed Articles
Chiller Systems Microprocessor Replacement
Knowledge Base Search
Keywords  
Article Type  
Chiller Systems Microprocessor Replacement

SUMMARY
This article describes how to replace the microprocessor in your legacy chiller system.

SYMPTOMS
After performing a chiller microprocessor controller replacement on a dual state "D Series" chiller the second stage programming functions are not showing up in the programming mode.

CAUSE
By default, legacy replacement microprocessors are shipped configured for single "S Series" stage operation

RESOLUTION
When field installing a replacement microprocessor controller on a dual stage unit, the controller needs to me setup for dual stage operations.

The following steps will get your into the "Factory" programming mode to set up the controller for dual stage operation:

1. From the normal running mode, press and hold the "UP" and "SYS Pump" buttons for 3-5 seconds. Be sure to press both buttons at the same time firmly.

2. When the controller goes into the Factory programming mode you will see "CFG" in the top screen. Note: This will look like a "CF6".

3. Press set TWO times until you see "CP" in the top screen and a "1" in the bottom screen. Using the "Up" or "Dn" button change the CP value in the bottom screen from 1 to 2.

4. Once the CP value has been changed, hit the "Set" button approximately nine more times until you see a "UPD" in the top screen. Once you see "UPD" press the set button one more time and the screen will flash indicating the CP change you made has been saved into the controllers memory.

You have now configured the controller for dual stage operation. It is recommended that you go into the standard configuration mode to complete programming for your site conditions.

APPLIES TO
All Legacy models with microprocessor controllers

Posted 5/10/2006 :: 508 views
 
Related Articles
Chiller System Microprocessor Programming

Need instant sales support?

Call our TOLL FREE support line: 1-877-988-5464

OR

Live chat by BoldchatPlus
CRM by Boldcenter

Need a FAST quote??

 

CLICK HERE

To register or login to your Quote Wizard account and save up to 40%


Order your CDKEY catalog TODAY!

Featured Affiliate
UsedChillerStore.com

For both Buyers and Sellers this site offers a NO COST, Effective and Easy alternative to expensive auction sites or resellers who charge commissions. Our goal is to provide sellers an way to expose their used chiller equipment to a vast numbers of qualified buyers while giving buyers the ability to locate the equipment they need as quickly as possible.


Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

Home | Chiller Solutions | Fluid Solutions | On-line Store | Affiliates | General Support | Contact Us | Site Map | Links
Questions or problems regarding this web site should be directed to support@Legacychillers.com.
Copyright © 2007 Legacy Chiller Systems (USA). All rights reserved.
Toll free within USA/CANADA  - 877-988-5464