Water loop piping system design
Chiller Installation, Startup, and Maintenance
Glycol - Adding to chiller loop
Chiller Systems Recommended Maintenance
Closed Loop Chiller System - Automatic Air Vents
Chiller Problems - Microprocessor Low Pressure error
Chiller System Microprocessor Programming
Chiller Problems - Microprocessor Low Flow error
Chiller Systems - Starting your Chiller
Chiller Systems - Flooded Condenser Valves
My Recently Viewed Articles
Chiller System Microprocessor Error Codes
Chiller System Microprocessor Error Codes

SUMMARY
This article introduces the new error codes for chiller systems' microprocessors.

SYMPTOMS
Effective 1-1-2006 an update was performed on the Legacy microprocessor controller that provides diagnostic information should a temperature or pressure sensor fail. Error codes are as follows:

"tSi" for the inlet temperature sensor error.

"tSo" for the outlet temperature sensor error.

"tL1" for compressor 1 low pressure sensor error.

"tL2" for compressor 2 low pressure sensor error.

"tH1" for compressor 1 high pressure sensor error.

"tH2" for compressor 2 high pressure sensor error.

CAUSE
Since these sensors extremely reliable components, in most case problem result from a poor or damaged wire connection.

RESOLUTION
Should one of the above errors occur:

1.Make sure there the gray protective coating is not damaged in any way.

2.Check the connections at the back of the microprocessor. Make sure all connections to the boards buss are tight. Make sure NOT to over tighten.

3.Make sure there are no strands of wire making contact with any other conductor or, cabinet or ground.

4.Make sure the wire shielding is secure and not touching the cabinet or ground.

After carefully performing the checks above, try swapping the sensor inputs at the board. For example if you are getting a “tSi” error initially and you swap sensor position on the board and the error changes to a “tSo” error, this would confirm that you have a bad sensor and so on.

APPLIES TO
All models with microprocessors shipped after 1-1-2006.

Posted 1/30/2006 :: 517 views
 
Related Articles
Chiller Problems - Microprocessor Low Flow error
Chiller Problems - Microprocessor Low Pressure error
Chiller Installation, Startup, and Maintenance

Need instant sales support?

Call our TOLL FREE support line: 1-877-988-5464

OR

Live chat by BoldchatPlus
CRM by Boldcenter

Need a FAST quote??

 

CLICK HERE

To register or login to your Quote Wizard account and save up to 40%


Order your CDKEY catalog TODAY!

Featured Affiliate
UsedChillerStore.com

For both Buyers and Sellers this site offers a NO COST, Effective and Easy alternative to expensive auction sites or resellers who charge commissions. Our goal is to provide sellers an way to expose their used chiller equipment to a vast numbers of qualified buyers while giving buyers the ability to locate the equipment they need as quickly as possible.


Buy/Sell used and new overstock chillers FREE at UsedChillerstore.com

Home | Chiller Solutions | Fluid Solutions | On-line Store | Affiliates | General Support | Contact Us | Site Map | Links
Questions or problems regarding this web site should be directed to support@Legacychillers.com.
Copyright © 2007 Legacy Chiller Systems (USA). All rights reserved.
Toll free within USA/CANADA  - 877-988-5464